4 - 3 4 - 3
MELSEC-
A
4 PROCEDURE UP TO DATA LINK
4.2 Mounting and Installation
4.2.1 Handling precautions
This section explains the precautions for handling the AJ65SBT-CLB.
!
CAUTION
Do not touch the terminals while the module is energized. Doing so may cause
malfunctions.
Be careful not to let foreign matter such as dust or wire chips get inside the module.
This may cause a fire, failure or malfunctions.
Do not disassemble or modify the module.
Doing so may cause a failure, malfunction, injury or fire.
Do not touch the conductive and electronic parts of the module directly.
Doing so may cause a malfunction or failure of the module.
Since the case of the module is made of resin, do not drop it or give it a shock.
Doing so may damage the module.
Tighten the terminal screws within the specified torque range.
Loose tightening may cause a short circuit or malfunction.
Overtightening may cause a short circuit or malfunction due to damage to the screws
or module.
When disposing of this product, handle it as industrial waste.
Use the module in the environment specified in this manual.
Failure to do so may cause an electric shock, fire, malfunction, or damage to or
deterioration of the product.
Securely fix the module with DIN rails or mounting screws, and securely tighten it
within the specified torque range of the mounting screws.
Loose tightening may cause a drop or malfunction.
Overtightening may cause a drop or malfunction due to damage to the screws or
module.
Be sure to shut off all phases of the external power supply used by the system
before mounting or dismounting the product to or from the panel. Failure to do so
may cause a failure or malfunctions of the module.
Before handling the module, always touch grounded metal, etc. to discharge static
electricity from the human body.
Failure to do so can cause the module to fail or malfunction.
(1) Tighten the module mounting screws within the following ranges.
Screw Location Tightening Torque Range
Module mounting screw (M4 screw) 78 to 108N cm
FG terminal block terminal screw (M3 screw) 42 to 58N cm
(2) A protective film is attached on the module’s surface for the purpose of scratch
prevention during transportation.
Prior to use, be sure to remove it.
(3) Mount a DIN rail while paying full attention to the following points.
(a) Applicable DIN rail model name (compliant to IEC 60715)
TH35-7.5Fe
TH35-7.5A1
(b) DIN rail mounting screw interval
The pitch of 200mm or less should be ensured for screwing.
(4) When mounting the AJ65SBT-CLB to a DIN rail, push the centerline of the DIN
rail hook at the module bottom with your finger until it clicks.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Melsec-A AJ65SBT and is the answer not in the manual?

Mitsubishi Melsec-A AJ65SBT Specifications

General IconGeneral
BrandMitsubishi
ModelMelsec-A AJ65SBT
CategoryControl Unit
LanguageEnglish

Related product manuals