5.2 Precaution when connecting the uninterruptive power supply
Be sure of the following terms when connecting the QS Series CPU Module system to the
uninterruptive power supply (abbreviated as UPS hereafter):
As for UPS, use the online power system or online interactive system with a voltage
distortion rate of 5% or less.
For the UPS of the commercial online power system, use Mitsubishi Electric's F Series
UPS (serial number P or later) (Ex.: FW-F10-0.3K/0.5K).
Do not use any UPS of the commercial online power system other than the F series
mentioned above.