10
DEVICE EXPLANATION
10.2 Internal User Devices
10.2.7 Link relay (B)
10 - 24
9
Parameters
10
Device Explanation
11
CPU Module Processing
Time
12
Procedure for Writing
Program to CPU ModuleAppendicesIndex
10.2.7 Link relay (B)
(1) Definition
Link relays are CPU module side relays used when refreshing the link relay (LB) data
of the MELECNET/H network module, etc. to the CPU module or when refreshing the
CPU module data to the link relays (LB) of the MELECNET/H network module, etc.
(2) Number of used N/O and N/C contacts
There are no restrictions on the number of contacts (N/O contacts, N/C contacts) used
in the program.
Figure 10.18 Link refresh
Figure 10.19 Link Relay
Link relayLink relay
B0
LB0
CPU module MELSECNET/H network module
Link refresh
setting range
Link refresh
X0
B0
T0
Y20
X1 B0
B100
X2 B0
B1FFF
SET B0
K20
No restrictions on the quantity used.
B0 switches ON at X0 OFF to ON.
The link relay (B0) ON can only be used for
internal CPU module processing, and cannot be
output externally.
B0 ON/OFF information is output from the output
module to an external destination.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Q03UD(E)CPU and is the answer not in the manual?

Mitsubishi Q03UD(E)CPU Specifications

General IconGeneral
BrandMitsubishi
ModelQ03UD(E)CPU
CategoryController
LanguageEnglish

Related product manuals