11 - 9
11.1 Scan Time
11.1.2 Time required for each processing included in scan time
11
CPU MODULE PROCESSING TIME
Note4
Table11.4 Program-end overhead time of interrupt program (B2)
CPU module Without high-speed start With high-speed start
Q00JCPU 175 s 150 s
Q00CPU 145 s 125 s
Q01CPU 135 s 120 s
Q02CPU 180 s 75 s
Q02HCPU, Q06HCPU, Q12HCPU, Q25HCPU,
Q02PHCPU, Q06PHCPU, Q12PHCPU, Q25PHCPU,
Q12PRHCPU, Q25PRHCPU
80 s 35 s
Q02UCPU 26s 7s
Q03UDCPU, Q03UDECPU 26 s 7 s
Q04UDHCPU, Q06UDHCPU, Q13UDHCPU,
Q26UDHCPU, Q04UDEHCPU, Q06UDEHCPU,
Q13UDEHCPU, Q26UDEHCPU
26 s 7 s
Table11.5 Overhead time of fixed scan execution type program
Note11.3
CPU module Without high-speed start With high-speed start
Q02CPU 380 s 230 s
Q02HCPU, Q06HCPU, Q12HCPU, Q25HCPU,
Q02PHCPU, Q06PHCPU, Q12PHCPU, Q25PHCPU,
Q12PRHCPU, Q25PRHCPU
165 s 100 s
Q02UCPU 73 s 25 s
Q03UDCPU, Q03UDECPU 73 s 24 s
Q04UDHCPU, Q06UDHCPU, Q13UDHCPU,
Q26UDHCPU, Q04UDEHCPU, Q06UDEHCPU,
Q13UDEHCPU, Q26UDEHCPU
72 s 23 s
Note4
Basic
Note11.3
Since the Basic model QCPU cannot use fixed scan execution type programs, it is not necessary
to be conscious of the overhead time of the fixed scan execution type program.
Basic
Note11.3

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Q03UD(E)CPU and is the answer not in the manual?

Mitsubishi Q03UD(E)CPU Specifications

General IconGeneral
BrandMitsubishi
ModelQ03UD(E)CPU
CategoryController
LanguageEnglish

Related product manuals