Chapter 2 Installation and Configuration
© National Instruments 2-21 NI PXI-8109 User Manual
The NI PXI-8109 controller includes the following LabVIEW RT
configuration switches:
Switch 1—Boot LabVIEW RT: Set this switch to ON to boot
LabVIEW RT.
Switch 2—Boot Safe Mode: Set this switch to ON to boot LabVIEW
RT into safe mode to reconfigure TCP/IP settings and to download or
update software from a host computer. This switch overrides the
behavior of Switch 1. Booting the controller into safe mode does not
start the embedded LabVIEW RT engine. After changing the settings
or software, reboot the controller with this switch OFF to resume
normal operation.
Switch 3—Disable Startup VI: Set this switch to ON to prevent VIs
from automatically running at startup if the controller becomes
inaccessible because of a startup VI.
Switch 4—Reset IP Address: Set this switch to ON to reset the
IP address and other TCP/IP settings to their factory defaults. Use this
switch if moving the controller to a different subnet or if the current
TCP/IP settings are valid.
Note By default, the target will automatically attempt to connect to the network using
DHCP. If the target is unable to initiate a DHCP connection, the target connects to the
network with a link-local IP address or
169.254.x.x.

Table of Contents

Other manuals for National Instruments PXI Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the National Instruments PXI Series and is the answer not in the manual?

National Instruments PXI Series Specifications

General IconGeneral
BrandNational Instruments
ModelPXI Series
CategoryChassis
LanguageEnglish

Related product manuals