22
Week program
You can program the ventilation unit to run in accordance with specific settings at fixed times during the day and week via a week pro-
gram.
> Week program
On the main screen in the top right side an icon will be displayed when the week program is active
> Select program Settings:
Standard setting:
Description:
Off / 1 / 2 / 3
Off
The control allows you to set 3 programs for different situati-
ons e.g.:
• Normal operation
• Holliday operation
> Edit program Description: The selected week program is now active and can be edited.
> Monday Settings: Here weekday is selected.
>Function 1 Settings: Here you select the function you want to edit.
> Start time Settings:
Standard setting:
Description:
Hours and minutes
6:00
Set the time for the program to start.
The program will run until the next change in the week program.
> Ventilation Settings:
Standard setting:
Description:
Level 1 / Level 2 / Level 3 / Level 4 / Off
Level 3
Select the desired fan speed level here.
> Temperature Settings:
Standard setting:
Description:
5 40 °C
22 °C
Set the desired room temperature here.
> Copy for next day Description: Once the values for the Monday program have been set, it is
possible to copy these to the next day.
The same settings are made for
all functions.
> Reset program Settings: You can reset the program by selecting the “Approve” icon.