25
Humidity control
The primary purpose of ventilation is to extract humidity from the house so it does not damage the building, and to achieve a good indo-
or climate. During long periods with sub-zero temperatures, air humidity in the house may fall to a level that is critical for the building
and for the indoor climate. Wooden floors, furniture and walls can be damaged by very dry air, which also whirls up dust, resulting in a
poor indoor climate.
This is rectified by an integrated humidity control system that maintains good, relative air humidity. When the average air humidity in
the house falls below a set level (default set at 30%), ventilation may be reduced. It will typically only be for a short period of time. This
will help avoid further reduction of the air humidity in the house.
The humidity control system also has a function that allows increased ventilation, should the air humidity increase, for instance when
having a bath. The risk of mould growth in the bathroom is reduced, and the bathroom mirror will rarely steam up.
The humidity control system follows the average air humidity level measured over the previous 24 hours. In this way the system auto-
matically adapts to summer and winter conditions.
> Humidity control
> Vent.low humidity Settings:
Standard setting:
Description:
Level 1 / Level 2 / Level 3 / Off
Level 1
When the current humidity drops below the low humidity level,
the ventilation unit switches to the set ventilation level.
Off means that the ventation at low humidity is de-activated.
> Low humidity level Settings:
Standard setting:
Description:
15 45%
30%
When current humidity below this value falls, the ventilation
level set above is activated.
> Vent.high humidity Settings:
Standard setting:
Description:
Level 2 / Level 3 / Level 4 / Off
Level 3
At high humidity levels, for instance when having a bath, the
unit changes to the set fan speed level.
Off means that the function Ventilation at high humidity is de-
activaded.
> Max time high humidity Settings:
Standard setting:
Description:
1 180 min. / Off
60 min.
The function “High humidity” stops when actual humidity falls
below 3% above the average air humidity.
However, this time limit will stop operation if it fails within the
set time period.
Off means that the function Max. time at high humidity is de-
activated.