NFS-320/E/C, NFS-320SYS/E Operations Manual — P/N 52747:E1 06/16/2011 41
Viewing and Printing a Read Status Read Status Operation
How to Read Status for Annunciator Selections
Annunciator Selection screens specify the information that displays
on ACS annunciators. From the “Read Status” screen, press 0, then
press the
ENTER key. You can now view Read Status for System
Functions as follows: press Z, enter S, enter annunciation selection
number (1-4), press the
ENTER key. Sample LCD displays for the Read
Status of Annunciator Selection are shown below:
Figure 4.7 Annunciator Selection 1 Screen
To view the next three annunciator selection screens, press the (NEXT SELECTION) key.
Figure 4.8 Annunciator Selection 2 Screen
If UDACT=N, the control panel displays the Annunciator Selections 3 and 4 screen, addresses
A20-A32, as shown below
:
Figure 4.9 Annunciator Selections 3 and 4 Screens
Figure 4.10 System Function Selection 5 Screen
Figure 4.11 System Function Selection 6 Screen
BLINK=01 The rate at which intelligent
control or monitor modules
blink during polling
BLINK=00: No blink
BLINK=01: Devices blink on
every poll.
BLINK=16: Devices blink every
16th poll.
ST=4 NFPA wiring style operation
for the SLC
4 – Style 4 SLC or
6 – both Style 6 and Style 7 SLC
ACS=N Use ACS Selection Groups N – No annunciator selected or
Y – Select and display ACS Selection
Groups
Parameter Description Settings
Table 4.1 System Function Parameters (2 of 2)
A1=Address
ACS selection group
ANNUN SELECTION1: A1=H A2=* A3=* A4=*
A5=* A6=* A7=* A8=* A9=* A10=* A11=*
S1
ANNUN SELECTION2: A12=* A13=* A14=*
A15=* A16=* A17=* A18=* UDACT=N
S2
ANNUN SELECTION3: A20=* A21=* A22=*
A23=* A24=* A25=* A26=* A27=* A28=*
ANNUN SELECTION4: A29=* A30=* A31=*
A32=*
S3
S4
REGION=0 TBL.REMIND=2 ALA.SCROLL=Y
LOCAL CONTROL=1 IP ACCESS=0 DCC-MODE=N
S5
FLASHSCAN LIDET LIMOD
Y Y
S6