42 NFS-320/E/C, NFS-320SYS/E Operations Manual — P/N 52747:E1 06/16/2011
Read Status Operation Viewing and Printing a Read Status
Figure 4.12 System Function Selection 7 Screen
SEC_RLY and SUP_RLY (0= turn on by Fire Alarm, 1= turn on by Security, 2= turn on by
Supervisory).
BAT_SIZE (1= battery size is greater than 26 Ahr, 0= less t han 26 Ahr).
C_DRILL (custom drill N= No custom drill, Y= Yes).
TERM_DATA (0= LCD80 Terminal using 7 bit data, 1= LCD80 Terminal using 8 bit data).
PRT_BAND (0= 2400, 1= 4800, 2= 9600).
Figure 4.13 System Function Selection 8 Screen
An Annunciator Selection screen shows the information that will display on the ACS annunciators.
The table below contains the ACS display selections.
An example of ACS selections in Annunciator Selection Screen 1:
Figure 4.14 Annunciator Selection Screen 1 Example
The figure above shows annunciator selections for addresses A1-A3 (addresses A4-A10, marked
with asterisks, are not selected)
1 through 9 Programmable Annunciator #1 through #9
0 Programmable Annunciator #10
A 8 Systems points + Zones 1-56
B Zones 57-99, 9 F zones, 8 R zones, 4 NAC
C Loop 1, Modules 1-64
D Not Used
E Loop 1, Modules 65-128
F Not Used
G Loop 1, Modules 129-159
H Loop 1, Detectors 1-64
I Not Used
J Loop 1, Detectors 65-128
K Not Used
L Loop 1, Detectors 129-159
M Not Used
N 8 Systems points + Zones 1-56, used for remote station communicator (TM-4)
O 8 Systems points + Zones 1-56, used for municipal box trip output (TM-4)
Annunciator addresses 1 to 19 can be programmed to any one of the above selections. If there is a UDACT,
selections A-M will be sent to Annunciator addresses 20 to 32 respectively.
Table 4.2 ACS Selection Groups
NODE: 000.XXX, STYLE7:N
THRESHOLD CHANNEL A:H, CHANNEL B:H
S7
SEC_RLY:1 SUP_RLY:2 BAT_SIZE:0 C_DRILL:N
TERM_DATA:0 PRT_BAUD:2 CHARGER:Y
S8
ANNUN SELECTION1: A1=H A2=C AC=* A4=*
A5=* A6=* A7=* A8=* A9=* A10=* A11=*
NOTE: An ACS selection marked with an asterisk (*) indicates no annunciator selection.

Table of Contents

Other manuals for Notifier NFS-320

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier NFS-320 and is the answer not in the manual?

Notifier NFS-320 Specifications

General IconGeneral
BrandNotifier
ModelNFS-320
CategoryControl Panel
LanguageEnglish

Related product manuals