175
Setting Tag Data Links Section 6-2
• Differences Found in the Device Type
Click the OK Button or the Close Button.
5. If multiple nodes have been selected, the following message will be dis-
played. Click the Yes Button.
The comparison results will be displayed in order of the selected nodes.
6-2-13 Starting and Stopping Tag Data Links
Automatically Starting Tag Data Links
Tag data links will start operating automatically immediately after the tag data
link parameters are downloaded from the Network Configurator. (They will
also start automatically when the power to the PLC is turned ON or the CPU
Unit is restarted.)
Starting and Stopping All Tag Data Links on the Network
Using the Network
Configurator
All tag data links on the network can be started and stopped by selecting I/O
Connection - Start/Stop from the Network Menu.
Starting and Stopping Tag Data Links for Individual Devices
Using the Network
Configurator
You can start and stop tag data links for individual devices using the following
buttons in the Monitor Device Dialog Box. This applies only to tag data links
for which the device is the originator. Access the Monitor Device Dialog Box
by selecting Monitor from the Device Menu.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron CJ1W-EIP21 - 10-2010 and is the answer not in the manual?

Omron CJ1W-EIP21 - 10-2010 Specifications

General IconGeneral
BrandOmron
ModelCJ1W-EIP21 - 10-2010
CategoryNetwork Hardware
LanguageEnglish

Related product manuals