4 Basic Operation
4 - 24
E5@C Digital Temperature Controllers User’s Manual (H174)
4-9 Determining PID Constants
(AT, ST, Manual Setup)
AT Operations
AT is started when either at-2 (100% AT) or at-1 (40% AT) is specified for the AT Execute/Cancel
parameter.
The TUNE indicator will light during execution.
Only the Communications Writing, RUN/STOP, AT Execution/Cancel, and Program Start parameters
can be changed during AT execution. Other parameters cannot be changed.
AT Calculated Gain
The AT Calculated Gain parameter sets the gain for when PID values are calculated using AT. When
emphasizing response, decrease the set value. When emphasizing stability, increase the set value.
AT Hysteresis
The AT Hysteresis parameter sets the hysteresis when switching ON and OFF for the limit cycle
operation during auto-tuning.
4-9-1 AT (Auto-tuning)
When AT is executed, the optimum PID constants for the set point at that time
are set automatically. A method (called the limit cycle method) for forcibly
changing the manipulated variable and finding the characteristics of the
control object is employed.
Either 40% AT or 100% AT can be selected depending on the width of MV
variation in the limit cycle. In the AT Execute/Cancel parameter, specify at-2
(100% AT) or at-1 (40% AT). To cancel AT, specify off (AT cancel).
Only 100% autotuning is supported for heating and cooling control or floating
position-proportional control.
If the Heating/Cooling Tuning Method parameter is set to any value other than
0 (same as heating control), the PID constants are set automatically for both
heating control and cooling control.
AT cannot be executed when control has stopped or during ON/OFF control.
The results of autotuning are saved in the following parameters in the
Adjustment Level: Proportional Band (P), Integral Time (I), Derivative Time
(D), Proportional Band (Cooling) (C-P), Integral Time (Cooling) (C-I), and
Derivative Time (Cooling) (C-D).
Adjustment Level
at
8.0
p
233
i
40
d
Proportional
Band (Cooling)
8.0
c-p
Integral Time
(Cooling)
233
c-i
Derivative Time
(Cooling)
40
c-d
Proportional
Band
Integral
Time
Derivative
Time
000
000

Table of Contents

Other manuals for Omron E5CC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5CC and is the answer not in the manual?

Omron E5CC Specifications

General IconGeneral
BrandOmron
ModelE5CC
CategoryTemperature Controller
LanguageEnglish

Related product manuals