6 Parameters
6 - 96
E5@C Digital Temperature Controllers User’s Manual (H174)
6-9 Communications Setting Level
psel
Protocol Setting Communications must be supported.
u-no
Communications Unit No.
bps
Communications Baud Rate
len
Communications Data Length CompoWay/F must be selected as the protocol.
sbit
Communications Stop Bits CompoWay/F must be selected as the protocol.
prty
Communications Parity
CompoWay/F or Modbus must be selected as the
protocol.
sdwt
Send Data Wait Time
• Each parameter is enabled when the power is reset.
• Match the communications specifications of the E5@C and the host computer. If multiple
devices are connected, ensure that the communications specifications for all devices in
the system (except the Communications unit number) are the same.
Related Parameter
Communications Writing (Adjustment Level): Page 6-21
Setting
* Writing with communications is enabled if you set the Protocol Setting parameter to component
communications, Host Link (FINS), MC protocol (format 4), or dedicated protocol (format 4).
Item Display Set values Settings Default
Protocol setting psel cwf/
mod
cmp
fins
mcp4
fxp4
CompoWay/F
Modbus
Component communications
Host Link (FINS)
MC Protocol (format 4)
Dedicated protocol (format 4)
cwf
Communications
Unit No.
u-no 0 to 99 0 to 99 1
Communications
baud rate
bps 9.6/19.2/38.4/57.6
(Kbps)
9.6/19.2/38. 4/57.6 (kbps) 9.6
Communications
data length
len 7 or 8 bits 7 or 8 bits 7
Stop bits sbit 1 or 2 bits 1 or 2 bits 2
Communications
parity
prty none/eVen/odd None, Even, Odd eVen
Send data wait
time
sdwt 0 to 99 0 to 99 (ms) 20