1 - 3
1 Introduction
E5@C Digital Temperature Controllers User’s Manual (H174)
1-1 Appearance, Features, and
Functions of the E5@C
1
1-1-3 Main Functions
This port allows you to change or set parameters from the Setup Tool even when the Digital Controller
is installed in a panel.
For details on particular functions and how to use them, refer to Section 3 Part Names and Basic Pro-
cedures and following sections.
Input Sensor Types
You can connect the following sensors and signals to the universal input.
Control Outputs
A control output can be a relay output, voltage output (for driving SSR), or linear current output,
depending on the model.
Adjusting PID Constants
You can easily set the optimum PID constants by performing AT (auto-tuning) with the limit cycle
method or by performing ST (self-tuning) with the step response method.
You can also add RT (robust tuning) to give priority to controlling stability.
Alarms
Standard Alarms
You can output an alarm when the deviation, process value, set point, or manipulated value
reaches a specified value.
You can also output alarms for the PV rate of change and for loop burnouts.
If necessary, a more comprehensive alarm function can be achieved by setting a standby
sequence, alarm hysteresis, auxiliary output close in alarm/open in alarm, alarm latch, alarm ON
delay, and alarm OFF delay.
HB and HS Alarms
With models with the optional HB and HS alarms, you can detect heater burnout and heater short
alarms based on CT inputs.
Integrated Alarm
You can output an integrated alarm if a standard alarm, HB alarm, or HS alarm turns ON.
Setup Tool Port on Front Panel of the E5EC, E5EC-B, E5AC, E5DC or
E5DC-B
1-1-3 Main Functions
Thermocouple (temperature input): K, J, T, E, L, U, N, R, S, B, W, PLII
Resistance thermometer (temperature input): Pt100, JPt100
Infrared Temperature Sensor (temperature input): ES1B
10 to 70°C, 60 to 120°C, 115 to 165°C, 140 to 260°C
Current input (analog input): 4 to 20 mA DC, 0 to 20 mA DC
Voltage input (analog input): 1 to 5 VDC, 0 to 5 V DC, 0 to 10 V DC, 0 to 50 mVDC*
* This range can be used only for E5CC-U Digital
Controllers and only if they are manufactured in
May 2014 or later (version 2.2 or higher).
000
000

Table of Contents

Other manuals for Omron E5CC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5CC and is the answer not in the manual?

Omron E5CC Specifications

General IconGeneral
BrandOmron
ModelE5CC
CategoryTemperature Controller
LanguageEnglish

Related product manuals