6 Parameters
6 - 6
E5@C Digital Temperature Controllers User’s Manual (H174)
* A parameter mask can be used to hide the displays of parameters that are not needed. The parameter mask
function is provided by the Setup Tool.
Setup Tool: CX-Thermo (EST2-2C-MV4)
This parameter is used to set the password to move to the Protect Level.
Precautions for Correct Use
Protection cannot be cleared or changed without the password. Be careful not to forget it. If you
forget the password, contact your OMRON sales representative.
pmsk
Parameter Mask Enable
This parameter is displayed only when a parameter
mask has been set from the Setup Tool.
This parameter turns the parameter mask function ON and OFF.
The parameter mask settings are not initialized when other settings are initialized.
Use the Setup Tool to initialize the parameter mask settings.
prlp
Password to Move to Protect Level
To prevent setting the password incorrectly, the U and O Keys or D and O Keys must
be pressed simultaneously to set the password.
Set this parameter to 0 when no password is to be set.
Related Parameters
Move to Protect Level (Protect Level): Page 6-3
000
Function
Setting
Setting range Default
on: Enabled, off: Disabled on
000
Function
Setting
Setting range Default
1999 to 9999 0
See
See

Table of Contents

Other manuals for Omron E5CC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5CC and is the answer not in the manual?

Omron E5CC Specifications

General IconGeneral
BrandOmron
ModelE5CC
CategoryTemperature Controller
LanguageEnglish

Related product manuals