6 Parameters
6 - 82
E5@C Digital Temperature Controllers User’s Manual (H174)
sub1
Auxiliary Output 1 Assignment There must be an auxiliary output 1.
sub2
Auxiliary Output 2 Assignment There must be an auxiliary output 2.
sub3
Auxiliary Output 3 Assignment There must be an auxiliary output 3.
sub4
Auxiliary Output 4 Assignment
There must be an auxiliary output 4.
• These parameters set the function to assign to auxiliary outputs 1 to 4.
*1 If c-o is assigned for standard control, a value equivalent to 0% will be output.
*2 · If heating/cooling control is selected for the E5CC, E5CC-B, E5CC-U, E5DC, or E5DC-B when
there is only one control output, the auxiliary output 2 terminal is assigned as the control
output for cooling. (If the Digital Controller has only one auxiliary output, an output is not
automatically allocated for the control output for cooling.)
· If heating/cooling control is selected for the E5EC, E5EC-B, or E5AC when there is only one
control output, the auxiliary output 4 terminal is assigned as the control output for cooling. (If
the Digital Controller has only two auxiliary outputs, auxiliary output 2 is allocated as the
control output for cooling.)
· When heating/cooling control is selected for the E5GC, auxiliary output 1 is assigned as the
control output for cooling.
000
Setting range Default
none: Disabled
Auxiliary Output 1 Assignment: alm1
*5
Auxiliary Output 2 Assignment: alm2
*2
Auxiliary Output 3 Assignment: alm3
*2
Auxiliary Output 4 Assignment: alm4
*2
o: Control output (heating)
c-o:
Control output (cooling)
*1
alm1:
Alarm 1
alm2:
Alarm 2
alm3:
Alarm 3
alm4:
Alarm 4
ha:
Heater alarm
hb:
HB alarm
hs:
HS alarm
s.err:
Input error
rs.er:
RSP input error
p.end:
Program end output
*3
run:
RUN output
alm:
Integrated Alarm
wr1:
Work bit 1
*4
wr2:
Work bit 2
*4
wr3:
Work bit 3
*4
wr4:
Work bit 4
*4
wr5:
Work bit 5
*4
wr6:
Work bit 6
*4
wr7:
Work bit 7
*4
wr8:
Work bit 8
*4

Table of Contents