6 - 85
6 Programless Communications
E5@C Digital Temperature Controllers Communications Manual (H175)
6-10 Connecting to MELSEC iQ-R-series PLCs
6
6-10-5 Checking Operation
With the default settings, the following parameters are set for the download areas.
(2) Initialize the download areas with the set values from the E5CC Controllers.
The download areas have not been initialized, so we will initialize them with the set values
from the E5CC Controllers.
Double-click D15 (Request Flag) on the Device Memory Dialog Box. A message will appear
asking if you want to register it to the Watch Tab Page. Click the Yes Button.
No.0 No.1 No.2 Parameter Value (E5CC default settings)
D15 D45 D75 Request Flag (fixed) 1 (0001 hex)
D16 D46 D76 Operation Command Code
(fixed)
0 (0000 hex)
D17 D47 D77 Set Point 0 (0000 hex)
D18 D48 D78 Proportional Band 80 (0050 hex)
D19 D49 D79 Integral Time 233 (00E9 hex)
D20 D50 D80 Derivative Time 40 (0028 hex)
D21 D51 D81 Alarm Value 1 0 (0000 hex)
D22 D52 D82 Alarm Value Upper Limit 1 0 (0000 hex)
D23 D53 D83 Alarm Value Lower Limit 1 0 (0000 hex)
D24 D54 D84 Alarm Value 2 0 (0000 hex)
D25 D55 D85 Alarm Value Upper Limit 2 0 (0000 hex)
D26 D56 D86 Alarm Value Lower Limit 2 0 (0000 hex)
D27 D57 D87 Heater Burnout Detection 1 0 (0000 hex)
D28 D58 D88 PV Input Shift 0 (0000 hex)
D29 D59 D89 SP Ramp Set Value 0 (0000 hex)

Table of Contents

Other manuals for Omron E5EC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5EC and is the answer not in the manual?

Omron E5EC Specifications

General IconGeneral
BrandOmron
ModelE5EC
CategoryTemperature Controller
LanguageEnglish

Related product manuals