2 - 17
2 CompoWay/F Communications Procedures
E5@C Digital Temperature Controllers Communications Manual (H175)
2-3 Detailed Description of the Services
2
2-3-8 Operation Command
(2) Response Code
• Normal Completion
• Error Occurred
(3) Operation Commands and Precautions
• Communications Writing
Set the Communications Writing parameter to "ON: enabled" or "OFF: disabled" with the related
information setting. The setting can be accepted in both setup area 0 and setup area 1. An
operation error will occur, however, if enabling or disabling communications writing is set for an
event input.
• RUN/STOP
Set control to “run” or “stop” with the related information setting. The setting can be accepted in
both setup area 0 and setup area 1. An operation error will occur, however, if RUN/STOP is set for
an event input.
0C
Alarm Latch Cancel 00: Alarm 1 latch cancel
01: Alarm 2 latch cancel
02: Alarm 3 latch cancel
03: HB alarm latch cancel
04: HS alarm latch cancel
05: Alarm 4 latch cancel
0F: All alarm latch cancel
0D
SP Mode 00: Local SP mode
01: Remote SP mode
0E
Invert Direct/Reverse Operation 00: Not invert
01: Invert
11
Program Start 00: Reset
01: Start
Response code Name Description
0000 Normal completion No errors were found.
Response code Error name Description
1001 Command too long The command is too long.
1002 Command too short The command is too short.
1100
Parameter error Command code and related
information are wrong.
2203
Operation error • The Communications Writing
parameter is set to "OFF"
(disabled). The command is
received regardless of the
Communications Writing
parameter setting (ON/OFF).
• Processing could not be
performed. For details, refer to
(3) Operation Commands and
Precautions below.
• Non-volatile memory error
Command code Command content Related Information