EasyManuals Logo

Omron NJ501-1400 User Manual

Omron NJ501-1400
400 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #28 background imageLoading...
Page #28 background image
Precautions for Safe Use
26
NJ-series CPU Unit Hardware User’s Manual (W500)
• Make sure that the required data, including the user program, configurations, settings, variables, and
memory used for CJ-series Units, is transferred to a CPU Unit that was replaced and to externally
connected devices before restarting operation.
Be sure to include the tag data link settings, routing tables, and other CPU Bus Unit data, which are
stored in the CPU Unit.
• The absolute encoder home offsets are backed up with a Battery in the CPU Unit as absolute
encoder information. When you change the combination of the CPU Unit and Servomotor, e.g., when
you add or replace a Servomotor, define the absolute encoder home again.
• The performance may be different if the hardware revisions are different. Before you transfer the user
program, data, and parameter settings to the CPU Units with the different hardware revisions, check
them for proper execution and then use them for actual operation.
• Dispose of the product and Batteries according to local ordinances as they apply.
• The following information must be displayed for all products that contain primary lithium batteries with a
perchlorate content of 6 ppb or higher when shipped to or transported through the State of California, USA.
Perchlorate Material - special handling may apply.
See www.dtsc.ca.gov/hazardouswaste/perchlorate.
• The CPU Unit contains a primary lithium battery with a perchlorate content of 6 ppb or higher. Place
the above information on the individual boxes and shipping boxes when shipping finished products
that contain a CPU Unit to the State of California, USA.
Unit Replacement
Disposal

Table of Contents

Other manuals for Omron NJ501-1400

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron NJ501-1400 and is the answer not in the manual?

Omron NJ501-1400 Specifications

General IconGeneral
BrandOmron
ModelNJ501-1400
CategoryControl Unit
LanguageEnglish

Related product manuals