15-33
15 Ethernet
CP2E CPU Unit Software User’s Manual(W614)
15-4 FINS Communications
15
15-4-6 New FINS Commands
Response Block
Parameters
Number of Records (Command, Response)
The number of records to read is specified between 0000 and 0008 (0 to 8 decimal) in the com-
mand. If this value is set to 0, the number of stored records will be returned but the IP router table
records will not be returned. The response returns the actual number of records read.
Maximum Number of Stored Records (Response)
The maximum number of records that can be stored in the IP router table is returned. The maximum
number of stored records is fixed at 0008 (8 records).
Number of Stored Records (Response)
The number of IP router table records stored at the time the command is executed is returned in
hexadecimal.
IP Router table Records (Response)
The number of IP router table records specified in the number of records parameter is returned. The
total number of bytes in the IP router table records is calculated as the number of records × 8
bytes/record. The configuration of the 8 bytes of data in each record is shown below.
• IP Network Address
The network ID from the IP address in hexadecimal. The network ID part corresponding to the
address class (determined by the leftmost 3 bits) set here, is enabled.
• Router IP Address
The IP address (in hexadecimal) of a router connected to a network specified with IP addresses.
Precautions for Correct UsePrecautions for Correct Use
If the IP router table contains fewer records than the number specified in the number of records
parameter, all the records contained in the IP router table when the command is executed will be
returned and the command execution will end normally.
Response Codes
Response code Description
0000 Normal
1004 Command format error
Maximum
number
of stored
records
Number
of stored
records
Number
of records
IP router
table records
Response
code
Command
code
27 61
IP router
table records
8 bytes 8 bytes
IP Network address
(Network ID)
Router IP address
1
8 bytes

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSMAC CP2E-N D Series and is the answer not in the manual?

Omron SYSMAC CP2E-N D Series Specifications

General IconGeneral
BrandOmron
ModelSYSMAC CP2E-N D Series
CategoryComputer Hardware
LanguageEnglish

Related product manuals