A - 20
NX-series Communications Interface Units User’s Manual (W540)
The following table shows the Input Sub Info. If the Input Data Type indicates a control command
response, the result of the control command is stored in the Input Sub Info.
*2. The value will be 2 hex only when the Number of Characters to Determine the End is set to a value other
than 0. If the Number of Characters to Determine the End is set to 0 and there is receive data, the value
will be 1 hex.
*3. If the Number of Characters to Determine the End is not set to 0, the value will be 1 hex when the final
receive data is received. The value will then change to 2 hex when the end is detected.
*4. Both data reception and a command response may occur at the same time.
*5. You cannot read this data as BOOL data. To read
the command code of a control command, access the
data as WORD data.
Value
(hex)
Execution result of
control command
Description
0000 Normal end Normal end
0001 Execution is not possi-
ble because an opera-
tion is in progress.
The RS Signal ON or RS Signal OFF control command was exe-
cuted when the flow control method was set to RS/CS flow control.
The Clear Serial Line Monitor Buffer control command was executed
whe
n
serial line monitoring was in progress.
0002 Undefined command An undefined control command was specified and therefore it cannot
be executed.
0003 Setting out-of-range
erro
r
The Change Number of Characters to Determine the End or Change
Communications Setup control command was executed and the
value of the Output Sub Info was out of range.
The Flow Control Method in the Output Sub In
fo
for the NX-CIF105
was set to RS/CS flow control.
Index
(hex)
Subindex
(hex)
Object name Default Data range Unit
Data
type
Access
I/O allo-
cation
Data
attri-
bute
7000 --- Ch1 Output Data --- --- --- --- --- --- ---
00 Ch1 Number of Entries 6 1 to 15 --- USINT RO No ---
01
Ch1 Output SID
*1
00 hex --- --- USINT RW Yes ---
02 Ch1 Input SID
Resp
onse
*2
00 hex --- --- USINT RW Yes ---
03 Ch1 Output Data Type
(See below for details.)
0000 hex --- --- WORD
and
BOOL
RW Yes --
-
04 Ch1 Output Sub Info
(See below for details.)
0000 hex --- --- WORD RW Yes ---
05 Ch1 Output Data
Le
ngth [b
ytes]
*3
0 --- --- UINT RW Yes ---
06 to 19 Ch1 Output Data 01 to
20
*4
00 hex
420
--- --- ARRAY
[0..3] OF
BYTE
RW Yes ---

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSMAC NX-CIF101 and is the answer not in the manual?

Omron SYSMAC NX-CIF101 Specifications

General IconGeneral
BrandOmron
ModelSYSMAC NX-CIF101
CategoryRecording Equipment
LanguageEnglish

Related product manuals