Rockwell Automation Publication SYSLIB-RM044D-EN-P - February 2017 17
PowerFlex 753 Drive (P_PF753)
PCmd_Fwd BOOL 0 When Cfg_PCmdClear is 1:
Set PCmd_Fwd to 1 to select the forward direction
Set PCmd_Rev to 1 to select the reverse direction
These parameters are reset automatically
When Cfg_PCmdClear is 0:
Set PCmd_Rev to 0 to select the forward direction
Set PCmd_Rev to 1 to select the reverse direction
PCmd_Fwd is not used
These parameters do not reset automatically
PCmd_Rev
PCmd_Acq BOOL Mode.PCmd_Acq 0 When Cfg_PCmdClear is 1:
Set PCmd_Acq to 1 to Acquire
Set PCmd_Rel to 1 to Release
These parameters reset automatically
When Cfg_PCmdClear is 0:
Set PCmd_Acq to 1 to Acquire
Set PCmd_Acq to 0 to Release
PCmd_Rel is not used
These parameters do not reset automatically
PCmd_Rel Mode.PCmd_Rel
PCmd_Lock BOOL Mode.PCmd_Lock 0 When Cfg_PCmdClear is 1:
Set PCmd_Lock to 1 to Lock
Set PCmd_Unlock to 1 to Unlock
These parameters reset automatically
When Cfg_PCmdClear is 0:
Set PCmd_Lock to 1 to Lock
Set PCmd_Lock to 0 to Unlock
PCmd_Unlock is not used
These parameters do not reset automatically
PCmd_Unlock Mode.PCmd_Unlock
PCmd_Reset BOOL 0 Set PCmd_Reset to 1 to reset all alarms requiring reset
This parameter is always reset automatically
PCmd_FailToStartAck BOOL FailToStart.PCmd_Ack 0 Set PCmd_<Alarm>Ack to 1 to Acknowledge alarm
The parameter is reset automatically
PCmd_FailToStopAck FailToStop.PCmd_Ack
PCmd_IntlkTripAck IntlkTrip.PCmd_Ack
PCmd_DriveFaultAck DriveFault.PCmd_Ack
PCmd_IOFaultAck IOFault.PCmd_Ack
PCmd_FailToStartSuppress BOOL FailToStart.PCmd_Suppress 0 When Cfg_PCmdClear is 1:
Set PCmd_<Alarm>Suppress to 1 to suppress alarm
Set PCmd_<Alarm>Unsuppress to 1 to unsuppress alarm
These parameters reset automatically
When Cfg_PCmdClear is 0:
Set PCmd_<Alarm>Suppress to 1 to suppress alarm
Set PCmd_<Alarm>Suppress to 0 to unsuppress alarm
PCmd_<Alarm>Unsuppress is not used
These parameters do not reset automatically
PCmd_FailToStopSuppress FailToStop.PCmd_Suppress
PCmd_IntlkTripSuppress IntlkTrip.PCmd_Suppress
PCmd_DriveFaultSuppress DriveFault.PCmd_Suppress
PCmd_IOFaultSuppress IOFault.PCmd_Suppress
PCmd_FailToStartUnsuppress FailToStart.PCmd_Unsuppress
PCmd_FailToStopUnsuppress FailToStop.PCmd_Unsuppress
PCmd_IntlkTripUnsuppress IntlkTrip.PCmd_Unsuppress
PCmd_DriveFaultUnsuppress DriveFault.PCmd_Unsuppress
PCmd_IOFaultUnsuppress IOFault.PCmd_Unsuppress
Table 8 - P_PF753 Drive Input Parameters
Input Parameter Data
Type
Alias For Default Description

Other manuals for Rockwell Automation PowerFlex 70

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation PowerFlex 70 and is the answer not in the manual?

Rockwell Automation PowerFlex 70 Specifications

General IconGeneral
BrandRockwell Automation
ModelPowerFlex 70
CategoryController
LanguageEnglish

Related product manuals