Switch Control Setup
Netlist Verbose Logging
When enabled, all Netlist-related event messages will be logged. The default is the
Disabled setting because Netlist logging quickly lls log memory and should only be
used for troubleshooting a specic situation.
IntelliTeam Verbose Logging
When enabled, all IntelliTeam restoration system event messages (excluding Netlist-
related events) will be logged. The default is the Disabled setting because IntelliTeam
system logging quickly lls log memory and should only be used for troubleshooting a
specic situation.
Comm Check Runner Timeout
When this timer expires before the Communications Check Runner cycle is complete,
the Netlist push is incomplete. (Range: 30-500 seconds; Step: 1; Default: 120)
Data Runner Start Delay
This sets the interval between the completion of one Data Runner cycle (to collect and
distribute real-time data) and the start of the next Data Runner cycle. (Range: 0-60;
Step: 1; Default: 3)
Data Runner Timeout
When this timer expires before the Data Runner cycle is complete, a new Data Runner
cycle is started. (Range: 20-120 seconds; Step: 1; Default: 30)
Request Timeout Delay
This sets the time interval between rmware upload completion and the subsequent
request for a new Netlist. This delay also applies when a new control is deployed, it will
wait this time interval before requesting a new Netlist. (Range: 1-65,535 seconds; Step:
1; Default: 40)
Report Periodic Delay
This sets the time interval between each Netlist transmission. (Range: 1-65,535 seconds;
Step: 1; Default: 60)
DNP-IP Address Mapping
Map IP addresses to DNP/RTU addresses for team members that are accessible only
over an Ethernet port. An entry must be included in this table for any team member
where Ethernet is the congured Comm Port to Use setting. The DNP Address value
is the DNP/RTU address for the IP-based team members. The IP Address value is the
IP address associated with the destination team members.
Figure 27. The Setup>Restoration>IntelliTeam SG>Distributed Generation screen.
These settings are used for IntelliTeam systems with distributed generation resources
(e.g. solar, wind, etc.) on the circuit. See Figure 27.
Distributed Generation