Technical Data
A-4
MP270 Equipment Manual
Release 01/99
Ambient conditions
Vibration
Operation 0.035 mm (10 – 58 Hz)
1 g (58 – 500 Hz)
Shipping, storage 3.5 mm (5 – 8,5 Hz)
1 g (8.5 – 500 Hz)
Max. pressure difference (front/rear side) 2 hPa
Barometric pressure
Operation
Shipping, storage
706 to1030 hPa
581 to 1030 hPa
Compliance of the named products with the regulations of Directive 89/336 EEC is
verified by conformance with the following standards:
Noise immunity
Static discharge
(contact discharge/air discharge)
EN 61000–4–2
6 kV/8 kV
RF irradiation EN 61000–4–3
10 V/m, 80% AM,
1 kHz
Pulse modulation ENV 50204
900 MHz "5 MHz
10 V/m
eff.
, 50% ED, 200 Hz
RF conduction EN 61000–4–6
150 kHz – 80 MHz
10 V, 80% AM, 1 kHz
Burst interference
Mains lines
Supply lines
Process data lines
Signal lines
EN 61000–4–4
2 kV
2 kV
2 kV
1 kV
Radio interference
Radio interference level complying to
EN 55011
Class A