Compact Series Product Overview
Technical Reference Manual
PXC-24 Supported Point Types.
Universal
Input (UI)
Points 1-3
Universal
Input/Output (U)
Points 4-12
Super Universal (X)
Points 13-16
Analog Output
(AO)
Points 17-19
Digital Output
(DO)
Points 20-24
Analog
Output
Voltage 0 to 10 Vdc
• • •
Current 0 to 20 mA
•
Digital
Output
Binary/Digital Output
•
4
•
1)
Platinum 1K 375 or 385 alpha.
2)
Siemens, Johnson Controls, and DIN Standard Nickel.
3)
10K and 100K Type 2 and 10K Type 3.
4)
Requires an external relay.
5)
Sensor supply 24 Vdc, 4.8W
PXC-36 Supported Point Types.
Super Universal
(X)
Points 1-6
Universal
Input/Output (U)
Points 7-24
Digital Input (DI)
Points 25-28
Digital Output (DO)
Points 29-36
Analog Input
5
Voltage 0 to 10 Vdc
• •
Current 4 to 20 mA
• •
RTD Pt 1K
1
• •
RTD Ni 1K
2
• •
Thermistor 10K NTC
3
• •
Thermistor 100K NTC
3
• •
Digital Input Status (Binary Input)
• • •
Pulse Accumulator (Counter)
• •
Analog
Output
Voltage 0 to 10 Vdc
• •
Current 0 to 20 mA
•
Digital
Output
Binary/Digital Output
•
4
•
1)
Platinum 1K 375 or 385 alpha.
2)
Siemens, Johnson Controls, and DIN Standard Nickel.
3)
10K and 100K Type 2 and 10K Type 3.
4)
Requires an external relay.
5)