Hardware Features
Memory
22
| 100
Siemens Industry, Inc.
145-172
Building Technologies
Restricted
2018-09-25
Flash Read-Only Memory (Flash ROM)
Flash Read-Only Memory (Flash ROM) is the non-volatile, permanent memory of the
PXC Compact, which stores the operating system, the APOGEE firmware, and the
language files. A limited amount of secondary storage is provided in Electrically
Erasable Programmable Read-Only Memory (EEPROM) for the field panel address or
name, communication speeds, and other set-up parameters. In the event of a power
surge, a power loss, or failure of the battery backup, the Flash ROM and EEPROM
contents stay intact.
PXC Compact Flash ROM size cannot be upgraded in the field.
Compressed ROM
The PXC Compact has a large amount of high performance RAM. To allow for future
features and to provide high system performance, the APOGEE firmware is stored in
ROM in a compressed state; it is de-compressed into RAM on system power-up. As a
result, the entire onboard RAM is not available for the point database, the PPCL
program, and trend data.
Auto-Restore and Database Backup to Flash
APOGEE Firmware Revision 2.8.4/3.1 and later supports Auto-Restore and Database
Backup to Flash.
Database Backup to Flash allows the user to manually save a copy of the
database in flash memory of the controller.
The field panel may be configured to automatically restore the database from flash
memory after a coldstart.
When auto-restore is enabled, a coldstart does not result in the same downtime
as with earlier revisions of APOGEE Firmware. Because there is no waiting on
a full download from the backup system, the database is restored from flash so
quickly that there is little to no downtime. However, the accumulated trend data
is deleted from memory.
Database restoration from flash is disabled by default.
When FLN Mode is selected for the PXC Compact or UEC, database
restoration from flash is automatically enabled.
When P1 Mode is selected for the PXC Compact, database restoration from
flash is automatically enabled and 128K of memory is reserved for ISB files.
The field panel may be configured to automatically restore the database from flash
memory after a coldstart.
When auto-restore is enabled, a coldstart does not result in the same downtime
as with earlier revisions of APOGEE firmware. Because there is no waiting on a
full download from the backup system, the database is restored from flash so
quickly that there is little to no downtime. However, the accumulated trend data
is deleted from memory.
Database restoration from flash is disabled by default.
For procedures on using Auto-Restore and Database Backup to Flash, see the
APOGEE P2 ALN Field Panel User's Manual (125-3019) or the APOGEE BACnet ALN
Field Panel User's Manual (125-3020).

Table of Contents

Other manuals for Siemens PXC Compact Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens PXC Compact Series and is the answer not in the manual?

Siemens PXC Compact Series Specifications

General IconGeneral
BrandSiemens
ModelPXC Compact Series
CategoryControl Unit
LanguageEnglish

Related product manuals