46/64
Building Technologies Division User Manual RWF50... CC1U7866en
Infrastructure & Cities Sector 8 Configuration ConF 25.07.2014
8.5 Binary input binF
This setting decides on the use of the binary input.
Reference!
See chapter 5.4 Predefined setpoint.
ConF binF
Parameter Value/
selection
Description
Binary input
bin1
Binary inputs
0 No function
1 Setpoint changeover
2 Setpoint shift
4 Changeover of operating mode
Burner modulating:
Contacts D1 and DG open
Burner 2-stage:
Contacts D1 and DG closed