Detailed descriptions
16.1 Motherboard
SIMATIC HMI IPC677C
200 Operating Instructions, 04/2013, A5E02722710-04
All ports are designed as high current USB (500 mA), you can only use a maximum of 2
simultaneously as high current, however.
NOTICE
No USB devices can be connected which feed back voltage to the Box PC.
PROFIBUS/MPI interface X4
PROFIBUS/MPI interface
1
Pin no. Short description Meaning Input / Output
1 – Unassigned –
2 – Unassigned –
3 LTG_B Signal line B of MPI module Input/output
4 RTS_AS RTSAS, control signal for received data
stream. The signal is "1" when the directly
connected AS is sending.
Input
5 M5EXT M5EXT return line (GND) of 5 V supply. The
current load of an external consumer
connected between P5EXT and M5EXT may
not exceed the 90 mA.
Output
6 P5 EXT P5EXT power supply (+5 V) of the 5 V power
supply. The current load of an external
consumer connected between P5EXT and
M5EXT may not exceed the 90 mA.
Output
7 – Unassigned –
8 LTG_A Signal line A of the MPI module Input/output
9 RTS_PG RTS output signal of the MPI module. The
control signal is "1" when the programming
device is sending.
Output
Shield on connector casing
1
Optional product variant

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC HMI IPC677C and is the answer not in the manual?

Siemens SIMATIC HMI IPC677C Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC HMI IPC677C
CategoryIndustrial PC
LanguageEnglish

Related product manuals