2.20 Protection Function Control
295
7UT613/63x Manual
C53000-G1176-C160-2
2.20.2 Tripping Logic for the Entire Device
2.20.2.1 General Tripping
All tripping signals of the protection functions are OR–combined and lead to the alarm
„Relay TRIP“. This can be allocated to an LED or output relay as can be each of the
individual trip commands. It is suitable as general trip information as well as used for
the output of trip commands to the circuit breaker.
Once a trip command is activated, it is stored separately for each protection function.
At the same time a minimum trip command duration TMin TRIP CMD is started to
ensure that the command is sent to the circuit breaker long enough if the tripping pro-
tection function should drop off too quickly or if the breaker of the feeding end operates
faster. The trip commands cannot be terminated until the last protection function has
dropped off (no function activated) AND the minimum trip command duration is over.
Figure 2-121 Storage and termination of the trip command (simplified)
Reclosure Inter-
locking
After tripping the circuit breaker by a protection function the manual reclosure must
often be blocked until the cause for the protection operation is found.
Using the user-configurable logic functions (CFC) an automatic reclosure interlocking
function can be created. The default setting of 7UT613/63x offers a pre-defined CFC
logic which stores the trip command of the device until the command is acknowledged
manually. The CFC block is illustrated in the Appendix under „Preset CFC Charts“.
The internal output „G-TRP Quit“ must be additionally assigned to the tripping
output relays which are to be sealed.
Acknowledgement is done via binary input „>QuitG-TRP“. With default configura-
tion, press function key F4 at the device front to acknowledge the stored trip com-
mand.
If the reclosure interlocking function is not required, delete the allocation between the
internal single-point indication „G-TRP Quit“ and the source „CFC“ in the configu-
ration matrix.
Note
The internal single-point indication „G-TRP Quit“ is not affected by the setting
option Block relay of the protection functions. If this indication is allocated to a trip
relay, this relay will be actuated in case of a trip of the protection functions, even if
Block relay is set for that function.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7UT635*-* N series and is the answer not in the manual?

Siemens SIPROTEC 7UT635*-* N series Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7UT635*-* N series
CategoryProtection Device
LanguageEnglish

Related product manuals