2.22 Additional Functions
311
7UT613/63x Manual
C53000-G1176-C160-2
phase concatenation (D windings). For standard vector groups, this information corre-
spond to the ends of the windings. In more unusual vector groups (which are created
by phase swapping), the phase assignment in the vector group is not always clear.
The thermal values are referred to the tripping temperature rise. For degrees of tem-
perature there are no referred values. However, since further processing of such
values (in CFC or when transmitted through serial interfaces) requires values without
dimension, arbitrary references have been chosen, which are contained in Table 2-15
in the column „% conversion“.
Table 2-15 Thermal Measured Values
1)
only for overload protection with thermal replica (IEC 60255-8): Address 142 THERM. OVERLOAD = th repl w. sens
2)
only for overload protection with hot-spot calculation (IEC 60354): Address 142 THERM. OVERLOAD = IEC354
3)
only if RTD box(es) available
4)
only for CFC and serial interfaces
2.22.3.2 Information List
Measured values Dimension % Conversion
4)
θ
L1
/θ
OFF
; θ
L2
/θ
OFF
;
θ
L3
/θ
OFF
1)
Thermal value of each phase, referred to
the tripping value
%
θ/θ
Trip
1)
Thermal resultant value, referred to the
tripping value
%
Ag.rate
2)
3)
Relative ageing rate L p.u.
Res Warn
2)3)
Load reserve to hot-spot/ageing alarm
(stage 1)
%
Res Alarm
2)
3)
Load reserve to hot-spot tripping (stage
1)
%
θ leg L1; θ leg L2; θ
leg L3
2)
3)
Hot-spot temperature for each phase (Y
winding or Z winding)
°C or °F
0 °C = 0 %
500 °C = 100 %
0 °F = 0 %
1000 °F = 100 %
θ leg L12; θ leg L23;
θ leg L31
2)
3)
Hot-spot temperature for each phase (D
winding)
°C or °F
θ RTD 1... θ RTD 12
3)
Temperature measured at the
Temperature detectors 1 to 12
°C or °F
No. Information Type of In-
formation
Comments
044.2611 Θ/Θtrip = MV Temperat. rise for warning and trip
044.2612 Θ/ΘtripL1= MV Temperature rise for phase L1
044.2613 Θ/ΘtripL2= MV Temperature rise for phase L2
044.2614 Θ/ΘtripL3= MV Temperature rise for phase L3
044.2615 Θ leg L1= MV Hot spot temperature of leg L1
044.2616 Θ leg L2= MV Hot spot temperature of leg L2
044.2617 Θ leg L3= MV Hot spot temperature of leg L3
044.2618 Θ leg L12= MV Hot spot temperature of leg L12
044.2619 Θ leg L23= MV Hot spot temperature of leg L23
044.2620 Θ leg L31= MV Hot spot temperature of leg L31
044.2621 Ag.Rate= MV Aging Rate
044.2622 ResWARN= MV Load Reserve to warning level
044.2623 ResALARM= MV Load Reserve to alarm level
204.2611 2Θ/Θtrip = MV O/L2 Temperat. rise for warning and trip