EasyManuals Logo
Home>Siemens>Protection Device>SIPROTEC 7UT635*-* N series

Siemens SIPROTEC 7UT635*-* N series User Manual

Siemens SIPROTEC 7UT635*-* N series
638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #326 background imageLoading...
Page #326 background image
2 Functions
326
7UT613/63x Manual
C53000-G1176-C160-2
Where transfer to a central device is possible, the request for data transfer can be ex-
ecuted automatically. It can be selected to take place after each protection pickup or
after a trip only.
2.22.8.2 Setting Notes
Other settings pertaining to fault recording (waveform capture) are found in the
submenu Oscillographic Fault Records of the Settings menu. Waveform capture
makes a distinction between the trigger instant for an oscillographic record and the cri-
terion to save the record (address 901 WAVEFORMTRIGGER). Normally the trigger is
the pickup of a protective element, i.e. the time 0 is defined as the instant picked up
by the first protection function. The criterion for saving may be both the device pickup
(Save w. Pickup) or the device trip (Save w. TRIP). A trip command issued by
the device can also be used as trigger instant (Start w. TRIP); in this case it is also
the saving criterion.
The actual storage time begins at the pre-fault time PRE. TRIG. TIME (address 904)
ahead of the reference instant, and ends at the post-fault timePOST REC. TIME (ad-
dress 905) after the storage criterion has reset. The maximum recording duration to
each fault (MAX. LENGTH) is entered in address 903. Recording to each fault may
take max. 5 seconds. A total of 8 records can be saved. However the total length of
time of all fault records in the buffer may not exceed 5 seconds.
An oscillographic record can be triggered and saved by a change in status of a binary
input or via the operating interface connected to a PC. Storage is then triggered dy-
namically. The length of a record for these special triggers is set in address 906
BinIn CAPT.TIME (upper bound is MAX. LENGTH, address 903). Pre-trigger and
post-dropout times are included. If the binary input time is set to ∞, then the length of
the record equals the time that the binary input is activated (static), or the MAX.
LENGTH setting in address 903, whichever is shorter.
2.22.8.3 Settings
Addr. Parameter Setting Options Default Setting Comments
901 WAVEFORMTRIGGER Save w. Pickup
Save w. TRIP
Start w. TRIP
Save w. Pickup Waveform Capture
903 MAX. LENGTH 0.30 .. 5.00 sec 1.00 sec Max. length of a Waveform
Capture Record
904 PRE. TRIG. TIME 0.05 .. 0.50 sec 0.10 sec Captured Waveform Prior to
Trigger
905 POST REC. TIME 0.05 .. 0.50 sec 0.10 sec Captured Waveform after Event
906 BinIn CAPT.TIME 0.10 .. 5.00 sec; ∞ 0.50 sec Capture Time via Binary Input

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7UT635*-* N series and is the answer not in the manual?

Siemens SIPROTEC 7UT635*-* N series Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7UT635*-* N series
CategoryProtection Device
LanguageEnglish

Related product manuals