Page #113 background image
Mounting
7.3 Assembly and disassembly with different mounting systems
SIRIUS - SIRIUS 3RA load feeders
Manual, 09/2016, A5E03656507520A/RS-AB/003
113
7.3.4
Mounting on base plate
Mounting on base plate
All load feeder components are delivered ready for base plate mounting. The components'
size dictates whether they are mounted on the base plate with or without DIN rail adapters.
Table 7- 10 Mounting on a base plate with or without DIN rail adapter, depending on size
Mounting on base plate
Size
Direct-on-line starter
Reversing starter
Without DIN rail adapter
S00, S0, S2
S00
With DIN rail adapter
S00, S0, S2, S3
S00, S0, S2, S3
7.3.4.1
Mounting on base plate without DIN rail adapter
Mounting on base plate without DIN rail adapter
All size S00 to S2 direct-on-line starters and size S00 reversing starters may be mounted
directly on the base plate.
The load feeder is screwed to the base plate. The device enclosures contain fastening holes,
as well as openings for screw-mounted push-in lugs.
CAUTION
Short-circuit hazard
In configurations with a limiter, insulation of the base plate is necessary to avoid a short-
circuit to the base plate in the event of a short-circuit of the motor starter protector. If the
limiter and the feeder are mounted on the DIN rail adapter, insulation is not required.

Table of Contents

Other manuals for Siemens SIRIUS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIRIUS and is the answer not in the manual?

Siemens SIRIUS Specifications

General IconGeneral
BrandSiemens
ModelSIRIUS
CategoryRelays
LanguageEnglish

Related product manuals