Mounting
7.2 Mounting and disassembling load feeders
SIRIUS - SIRIUS 3RA load feeders
Manual, 09/2016, A5E03656507520A/RS-AB/003
51
Mounting an S3 load feeder with screw-type connection system
The S3 load feeder can only be mounted in combination with a DIN rail adapter onto a DIN
rail or a base plate.
Mounting the S3 load feeder is described in the chapter titled "Mounting direct-on-line
starters and reversing starters on DIN rail adapters (size S3) (Page 83)"
7.2.3
Load feeder with spring-loaded connection system
Mounting an S00 load feeder with spring-loaded connection system
Insert the connectors (a) on the link module into the corresponding main conductor
terminals (a) on the contactor. Make sure that the guide tabs are inserted into the slots (c) on
the contactor.
The link module will sit flush with the contactor on the left- and right-hand sides.
Figure 7-4 Mounting an S00 load feeder with spring-loaded connection system