05.2006 Parameterizing Steps
Siemens AG 6SE7087-2JD60
SIMOVERT MASTERDRIVES Operating Instructions 9-37
Parameter assignments depending on setpoint source (P368) and control type (P100):
P368 = Setpoint source
Parameter description
P368 = 0
PMU +
MOP
P368 = 1
Analog
inp. +
terminals
P368 = 2
FSetp +
terminals
P368 = 3
MOP +
terminals
P368 = 4
USS
P368 = 6
PROFI-
BUS
P368 = 7
OP1S +
FSetp
P368 = 8
OP1S +
MOP
P554.1 Src ON/OFF1 B0005 B0022 B0022 B0022 B2100 B3100 B2100 B2100
P555.1 Src OFF2 1 B0020 B0020 B0020 B2101 B3101 1 1
P561.1 Src InvRelease 1 B0016 1 1 1 1 1 1
P565.1 Src1 Fault Reset B2107 B2107 B2107 B2107 B2107 B2107 B2107 B2107
P567.1 Src3 Fault Reset 0 B0018 B0018 B0018 0 0 0 0
P568.1 Src Jog Bit0 0 0 0 0 B2108 B3108 B2108 0
P571.1 Src FWD Speed 1 1 1 1 B2111 B3111 B2111 1
P572.1 Src REV Speed 1 1 1 1 B2112 B3112 B2112 B2112
P573.1 Src MOP Up B0008 0 0 B0014 0 0 0 B2113
P574.1 Src MOP Down B0009 0 0 B0016 0 0 0 B2114
P580.1 Src FixSetp Bit0 0 0 B0014 0 0 0 0 0
P581.1 Src FixSetp Bit1 0 0 B0016 0 0 0 0 0
P590 Src BICO DSet B0014 * 0 0 0 0 B0014 B0014 * B0014 **
P651.1 Src DigOut1 B0107 * B0107 B0107 B0107 B0107 B0107 B0107 * B0107 *
P652.1 Src DigOut2 B0104 * B0104 B0104 B0104 B0104 B0104 B0104 * B0104 *
P653.1 Src DigOut3 0 * B0115 0 0 0 0 0 * 0 *
P654.1 Src DigOut4 0 0 0 0 0 0 0 0
Setpoint conn. parameter KK0058 K0011 KK0040 KK0058 K2002 K3002 KK0040 KK0058
* For factory setting P366 = 2, 3
♦ P590 = B0012
♦ P651 = B0000
♦ P652 = B0000
♦ P653 = B0107
** For factory setting P366 = 4:
♦ P590 = B4102
Bxxxx = Binector (Digital signal; values 0 and 1)
Kxxxx = Connector (16-bit signal; 4000h = 100 %)
KKxxxx = Double connector (32-bit signal; 4000 0000h = 100 %)
v/f characteristic + n/f-control: Setpoint connector parameter
(Setp-KP) = P443
T-control + n/f control: Setpoint connector parameter