HGM400 Series Genset Controller User Manual
HGM400 Series Genset Controller ISSUE 2015-05-27 Version 1.6 Page 11 of 44
4.3 AUTOMATIC START/STOP OPERATION
Auto mode is selected by pressing the button; a LED besides the button will
illuminate to confirm the operation.
Auto Start Sequence,
1) HGM420: when mains is abnormal (over/under voltage, loss of phase), enter into
“Mains Abnormal Delay and LCD displays count down time. Start Delay timer is
initiated after the delay has expired.
2) HGM410: WhenRemote Start is active,Start Delay” timer is initiated;
3) “Start Delay” countdown will be displayed on LCD;
4) When start delay is over, preheat relay energizes (if configured), preheat delay XXs
information will be displayed on LCD;
5) After the above delay, the Fuel Relay is energized, and then one second later, the
Start Relay is engaged. The engine is cranked for a pre-set time. If the engine fails to
fire during this cranking attempt then the fuel relay and start relay are disengaged for
the pre-set rest period; “crank rest time” begins and wait for the next crank attempt.
6) Should this start sequence continue beyond the set number of attempts, the start
sequence will be terminated, the fourth line of LCD display will be highlighted with