- 108 -
No.EX##-OMY0004
E4: Validation
Device type/equipment identification
Have all the mandatory requirements for the “Planning”
checklist been met?
Have all the mandatory requirements for the “Assembly and
electrical installation” checklist been met?
Have all the mandatory requirements for the “Startup and
parameterization” checklist been met?
Does the parameterization of the safe outputs correspond to
the version and the actual connection of the controlled device?
Has the assignment of the actuators to the outputs and the
variables of the safe application program been tested(online
status in SafetyProg)?
Has a function test been performed to check all safety
functions, in witch the module is involved?
Have measures been taken to achieve a specific Cat.?
Do all cables correspond to he specifications?
Does the voltage supply correspond to the specifications for
the protective extra-low voltage in accordance with PELV?
Have the voltage supply of US1 and US2 in system from a
power supply unit been implemented?
Is external protection of the module implemented (according to
the specifications in this user manual for supply voltage US1
and US2)?
Have measures been taken to prevent simple manipulation?
Are the requirements for the actuators and cable installation
observed according to the SIL/SILCL/Cat./PL?
Are the specifications for the parameterization for each
channel implemented?
Are test intervals specified for testing the shutdown capability
of the actuators, if this is required to achieve a
SIL/SILCL/Cat./PL?
Has it been ensured that any person intentionally starting
hazardous movements can only do so with a directly view of
the danger zone?
Signature (test engineer)