1sensorintheoutdoorair,installedinsidetheunitbeforethesupplyairfilteronthecoldsideof
theheatexchanger
1sensorinthesupplyairtobeplacedinthesupplyairductbytheinstaller
1sensorintheexhaust,installedinsidethe
unit
k.6.13Dampermotors
Fourdifferenttypesofdampermotorsareavailable;
On/offdampermotor,notmodulating,withoutspringfunction.Torqueis20Nmandruntimeis
150seconds
On/offdampermotor,modulating,withoutspringfunction.Torqueis20Nmandruntimeis150
seconds
Springreturndampermotor,not
modulating,withspringfunction.Torqueis20Nmandruntime
is150/16seconds
Springreturndampermotor,modulating,withspringfunction.Torqueis20Nmandruntimeis
150/16seconds
k.6.14Filterguards
Filterguardoverprefilterandprimaryfilterinstalledandconnectedtothecontrollerfordisplayofalarm
whenthemechanicallysetlimitisexceeded.FilteralarmwillbedisplayedontheSystemairControlPanel.
k.6.15Roomtemperaturesensors
Oneortwoexternalroomtemperaturesensorsareavailable.Thecabinethasbeenpreparedwith
additionalterminalsforconnectionoftheroomtemperaturesensors.Thesensorsaredeliveredwithout
cable.Thecontrollercalculatesanaverageofthevaluefromthe2sensorsasinputforthecontrol.
k.6.16Frostprotection
Forthefrostprotectionoftheheatingcoil,thewatertemperatureinthecoilis transmittedtothe
controllerbyatemperaturesensorinawaterreturncircuitofthecoil.Thecontrolleralwaysgeneratesa
signaltothevalvemotorthatkeepsasufficientflowofhotwatertoprotect
thecoilagainstfrost.Thisfrost
protectionisalsoactivatedwhentherunningmodeis“off”.
Ifthewatertemperaturefallsbelowthesetpointtemperaturethefansstop,thedampersclose,andan
alarmisactivated.
FromSystemaireveryheatingcoilforhotwaterisprovidedwithalittle
pipeatthecollectionpipeforthe
returnwater.Thislittlepipeispreparedfortheinstallationoftheabovementionedtemperaturesensorfor
thetransmissionofthereturnwatertemperaturetothecontroller.
k.6.17SystemairControlPanel‐SCP
Theseparatecableconnected(10m)handterminalwithdisplayandbuttonstheSystemairControlPanel
isalwaysnecessaryforthenormalhandlingandprogramming,becausethemainSyste mairE28controller
iswithoutdisplayandbuttons.
k.6.18Coolingrecovery
Iftheextractairtemperatureislowerthantheoutdoorairtemperature,andthereisacoolingdemandin
therooms,thecoolingrecoverywillbeactivatedbyreversingtheheatexchangersignal.Thesignalis
increasedtothecoolingrecoverybyincreasingcoolingdemand.
k.6.19Freecooling
Atemperaturesensorhasbeeninstalledinsidetheunitintheoutdoorairentrance.Iftheoutdoor
temperatureaftermidnightisbelowtheroomtemperaturesetpointandtheactualaverageroom
temperatureisabovethesetpointtemperature,thefansstartduringthesummertocooldownthe
buildingduring
nighthours.

Table of Contents

Other manuals for SystemAir Danvent DV

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SystemAir Danvent DV and is the answer not in the manual?

SystemAir Danvent DV Specifications

General IconGeneral
BrandSystemAir
ModelDanvent DV
CategoryAir Handlers
LanguageEnglish

Related product manuals