Othermotordrivenpartsaredamperswithdampermotorsandrotaryheatexchangers,butthemovement
issoslowthatguardmeasuresarenotnecessary.Justkeepyourhandsawayfromplaceswithriskofinjury.
Useparticulaterespiratorwhenfiltersarereplaced.
s.1.1Necessaryprotectionmeasurespriortostartup.
Ensurethatallprotectionmeasuresareinstalledcorrectbeforestartup.
s.1.1.1Designofprotectionmeasures
Insidethedoorsareadditionalprotectioninstalledguards thatonlycanberemovedbyuseoftools.
s.1.1.2Configurationoffrequencyconverterswithinstalledguard
Afrequencyconverterismountedbesidethefanin
someunits.Iftheconfigurationoffrequencyiscarried
outwiththefaninoperation,theguardmustbeinstalledforsafetyreasonsandalongcablemustbe
installedbetweenthefrequencyconverterinsidetheunitandthecontrolpaneloutsidetheunit.
s.1.2Safeadjustmentandmaintenance
Beforemaintenanceandrepair,theunitmustbeswitchedoffbyswitchingofftheautomaticcircuit
breakersandblockthembypadlocks.TheautomaticcircuitbreakersaremarkedF1toF4.Seethe
illustrationbelowabouthowtoplaceapadlockoneachautomaticcircuitbreaker.Checkthatthe
automaticcircuit
breakermarkedF5isstillswitchedonbecausethelampsinsidetheunit,andonlythose
lamps,areconnectedtothisswitch.Switchonthelampsforlightduringthemaintenanceactivities(note
thatthelampsareanaccessoryonlyinstalled,ifordered).
Usecutresistantglovesforprotection
againstinjuryfromsharpmetalplateedges.UseCEmarkedgloves
forthispurpose.Usehelmetduringmaintenanceworkintheunit.
s.1.3Personalprotectiveequipmentformaintenancestaffhealthandsafety
Usethebelowmentionedpersonalprotectiveequipmentformaintenance:
Cutresistantglovesforprotectionagainstinjuryfromsharpmetalplateedges.UseCEmarked
glovesforthispurpose.
Helmet
Particulaterespiratormaintenancefreeincludingfoamfacesealandadjustableprethreaded
headbandsforreplacingfilters.
Padlockforlockingtheabovementionedautomaticcircuitbreakers.
Permanentmagnetmotor.Theshaftmustbeblockedduringrepairsandmaintenanceofthe
electricsystem(themotorgenerateselectricitybyrotationforexamplethatthewindand
thermicdrivesthefan/motor).

Table of Contents

Other manuals for SystemAir Danvent DV

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SystemAir Danvent DV and is the answer not in the manual?

SystemAir Danvent DV Specifications

General IconGeneral
BrandSystemAir
ModelDanvent DV
CategoryAir Handlers
LanguageEnglish

Related product manuals