4. Tools
: R410A tools available
: Partly unavailable, : R410A tools unavailable
Tools / Equipment specification
1 Flare tool Clutch type Pipe flaring
2
Copper pipe gauge for
adjusting projection
margin
Flaring by
conventional
flare tool
3 Torque wrench
Tightening of
flare nut
䕿䖷
4 Gauge manifold
Port size
1/2"-20UNF
(5/16" Flare)
䕿䚷Note 2
5 Charge hose High-voltage 䕿䖷
6 Vacuum pump
Vacuum
drying
䕿䚷Note 3
1/2"-20UNF(5/16" Flare)
Connection
diameter 1/4"
7 Vacuum pump adapter
Vacuum
drying
䕿䚷Note 4
1/2"-20UNF(5/16" Flare)
Connection
diameter 1/4"
8
Electronic balance for
refrigerant charging
For 10 kg or
20 kg cylinder
Refrigerant
charge
䕿䕿
9 Leakage detector
Gas leakage
check
䕿䚷Note 5 䕿䚷Note 5
10 Refrigerant cylinder
Refrigerant
charge
䖷䚷Note 6
11
Refrigerant recovery
cylinder
Exclusive for
R32
Refrigerant
recovery container
䖷䚷Note 7
12
Refrigerant recovery
device
Refrigerant
recovery device
䕿䚷Note 8
Connection
diameter 1/4"
Note 1 When flaring is carried out for R410A or R32 using the conventional flare tools, adjustment of
projection margin is necessary. For this adjustment, a copper pipe gauge,
etc. are necessary.
Note 2 When saturation temperature is described, the gauge manifold differs for R410A and R32.
If saturation temperature reading is required, special tools exclusive for R32 are required.
Note 3 Since R32 has a slight possibility of burning, be sure to use the tools corresponding to R32.
Note 4 Like R410, a Vacuum pump adapter needs installing to prevent a Vacuum pump oil (mineral oil) from
flowing backward into the Charge hose. Mixing of the Vacuum pump oil into R32 refrigerant may
cause a trouble such as generation of sludge, clogging of capillary, etc.
Note 5 Be sure to use those tools after confirming they correspond to each refrigerant.
Note 6 For a refrigerant cylinder exclusive for R32, the paint color (or label color) of the cylinder is set
the specified color (light blue) together with the indication of the refrigerant name.
Note 7
Although the container specification is the same as R410A, use a recovering container exclusive
for R32 to avoid mixing with other refrigerants.
Note 8 Be careful for miss-charging of the refrigerant during work. Miss-charging of the refrigerant type
may cause not only damage of the equipments but also a fire etc.
In addition to the above exclusive tools, the following equipments are necessary as the general tools.
6) Spanner or Monkey wrench
7) Hole core drill
8) Tape meas
ure
9) Metal saw
1) Pipe cutter
2) Ream
er
3) Pipe bender
4) Level vial
5) Screwdriver
(+, –)
Also prepare the following equipments for other installation method and run check.
1) Clamp meter
2) Thermometer
3) Insulation resistance tester (Megger)
4) Electroscope
Evacuating,
refrigerant
charge, run
check, etc.
Installation/service tools
Use
Applicability to R32 air
conditioner or not
Applicability to R22 air
conditioner or not
No
General tools
ToolsexclusiveforR410A(ThefollowingtoolsforR410Aarerequired.)
FILE NO. SVM-18043

Table of Contents

Other manuals for Toshiba RAV-GM1101ATP-E

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba RAV-GM1101ATP-E and is the answer not in the manual?

Toshiba RAV-GM1101ATP-E Specifications

General IconGeneral
BrandToshiba
ModelRAV-GM1101ATP-E
CategoryAir Conditioner
LanguageEnglish

Related product manuals