3. Current release control
The output frequency and the output voltage are controlled by AC current value detected by current transformer
on the outdoor P.C. board so that input current of the inverter does not exceed the specified value.
I1
I1 – 0.5
Current [A]
Frequency down
Normal operation
Hold
Hold
Model
GM56 GM80
COOL HEAT COOL HEAT
I1 value [A]
10.1 12.0 14.5 14.0
Model
GM110 GM140
COOL HEAT COOL HEAT
I1 value [A]
21.2 21.2 21.2 21.2
4. Outdoor fan control
Allocations of fan tap revolutions [rpm]
Model W1 W2 W3 W4 W5 W6 W7 W8 W9 WA WB WC WD WE WF
GM56
200 300 350 410 480 500 530 560 640 670 700 750 800 840 950
GM80
200 300 350 410 480 500 530 560 640 670 700 750 840 980 1050
GM110
200 210 250 320 390 460 530 600 660 730 770
840 880 930 930
GM140
200 210 250 320 390 460 530 600 660 730 770
840 880 930 930
4-1. Cooling fan control
1) An outdoor fan is controlled by TL sensor, TO sensor and compressor frequency. An outdoor fan is
controlled at 1-tap interval of DC fan control.
2) At the start time, the fan is fixed for 60 seconds only with the maximum fan tap corresponded to the zone
in the following table but it is controlled with TL sensor temperature after then.
+ 1 tap / 20 sec (Up to the maximum
rotational frequency of each zone)
Rotational frequency hold
– 1 tap / 20 sec
(Up to the minimum rotational
frequency of each zone)
GM56, 80 : WE tap
GM110, 140 : WD tap
TL
55˚C
38˚C
35˚C
58˚C
Temp.
range
GM56
34.2 Hz or lower 34.2Hz to 58.8Hz 58.8Hz or higher
GM80
46.8 Hz or lower 46.8Hz to 83.4Hz 83.4Hz or higher
Min. Max. Min. Max. Min. Max.
38°C ≤ TO W6 WB W8 WE WA WE
29°C ≤ TO < 38°C W5 WA W7 WE W9 WE
15°C ≤ TO < 29°C W3 W7 W5 W9 W7 WB
5°C ≤ TO < 15°C W2 W5 W4 W7 W6 W9
0°C ≤ TO < 5°C W1 W3 W3 W5 W4 W7
–4°C ≤ TO < 0°C W1 W2 W2 W4 W3 W5
TO < –4°C OFF OFF OFF W3 W1 W4
TO error OFF WB OFF WE W1 WE
Temp.
range
GM110
GM140
34.2 Hz or lower 34.2Hz to 52.2Hz 52.2Hz or higher
Min. Max. Min. Max. Min. Max.
38°C ≤ TO W6 WD W8 WD WA WD
29°C ≤ TO < 38°C W5 WC W7 WC W9 WD
15°C ≤ TO < 29°C W3 W7 W5 W9 W7 WB
5°C ≤ TO < 15°C W2 W5 W4 W7 W6 W9
0°C ≤ TO < 5°C W1 W3 W3 W5 W4 W7
–4°C ≤ TO < 0°C W1 W2 W2 W4 W3 W5
TO < –4°C OFF W2 OFF W4 OFF W4
TO error OFF WD OFF WD OFF WD