EasyManuals Logo

Toshiba RAV-GM1101ATP-E User Manual

Toshiba RAV-GM1101ATP-E
127 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #73 background imageLoading...
Page #73 background image
Resistance (kΩ) (50˚C or lower)
Resistance (kΩ) (50˚C or higher)
0
0
50
100
150
200
0
5
10
15
20
10 20 30 40 50 60 70 80 90 100
Temperature (˚C)
Resistance (kΩ)
0
0
10
20
30
40
10 20 30 40 50 60 70 80 90 100
Temperature (˚C)
8-2-5. Diagnostic Procedure for Each Check Code (Outdoor Unit)
TD, TL sensors
Representative value
TA, TC, TCJ, TE, TS, TO sensors
TD, TL sensors
Temperature
(°C)
0
10
20
25
30
40
50
60
70
80
90
100
Resistance value (k
ΩΩ
ΩΩ
Ω)
(Minimum value) (Standard value) (Maximum value)
32.33 33.80 35.30
19.63 20.35 21.09
12.23 12.59 12.95
9.75
10.00 10.25
7.764 7.990 8.218
5.013 5.192 5.375
3.312 3.451 3.594
2.236 2.343 2.454
1.540 1.623 1.709
1.082 1.146 1.213
0.7740 0.8237 0.8761
0.5634 0.6023 0.6434
Temperature
(°C)
0
10
20
25
30
40
50
60
70
80
90
100
Resistance value (k
ΩΩ
ΩΩ
Ω)
(Minimum value) (Standard value) (Maximum value)
150.5 161.3 172.7
92.76 99.05 105.6
58.61 62.36 66.26
47.01 49.93 52.97
37.93 40.22 42.59
25.12 26.55 28.03
17.00 17.92 18.86
11.74 12.34 12.95
8.269 8.668 9.074
5.925 6.195 6.470
4.321 4.507 4.696
3.205 3.336 3.468
TA, TC, TCJ, TE, TS, TO sensors
Representative value
As TH sensor (Outdoor unit heat sink temp. sensor) is incorporated in the outdoor control P.C. board, the
resistance value cannot be measured.
Temperature sensor Temperature – Resistance value characteristic table
- 73 -
FILE NO. SVM-18043

Table of Contents

Other manuals for Toshiba RAV-GM1101ATP-E

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba RAV-GM1101ATP-E and is the answer not in the manual?

Toshiba RAV-GM1101ATP-E Specifications

General IconGeneral
BrandToshiba
ModelRAV-GM1101ATP-E
CategoryAir Conditioner