AC-SVX001A-EN
103
Table 28. Diagnostics communication (continued)
Diagnostic
Name
Affects
Target
Severity
Persistence
Active
Modes
[Inactive
Modes]
Criteria
Reset
Level
Comm Loss:
Local BAS
Interface
Chiller Info NonLatch All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second
period.
Use last valid BAS setpoints.
Diagnostic is cleared when successful
communication is established with the LonTalk LLID
(LCIC) or BacNet LLID (BCIC).
Remote
Comm Loss:
Off-cycle
Freeze
Protection
Relay
Chiller Info Latch All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second
period.
Remote
Comm Loss:
Oil Loss Level
Sensor Input
Ckt1
Circuit Normal Latch All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period
Remote
Comm Loss:
Oil Loss Level
Sensor Input
Ckt2
Circuit Normal Latch All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period
Remote
Comm Loss:
Oil Pressure
Cprsr1A
Circuit Immediate Latch All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period
Remote
Comm Loss:
Oil Pressure
Cprsr2A
Circuit Immediate Latch All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period
Remote
Comm Loss:
Op Status
Programmable
Relays
None Info Latch All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period
Remote
Comm Loss:
Outdoor Air
Temperature
Chiller
Normal
Shutdown
Latch All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second
period. For RTAE if this diagnostic occurs, operational
pumpdown will be performed regardless of the last
valid temperature
Remote
Comm Loss:
Suction Rfgt
Pressure Ckt1
Circuit Immediate Latch
All [Ckt/Cprsr
lock out]
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second
period. Note: This diagnostic is replaced by
diagnostic 5FB below with Rev 15.0
Remote
Comm Loss:
Suction Rfgt
Pressure Ckt2
Circuit Immediate Latch
All [Ckt/Cprsr
lock out]
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second
period. Note: This diagnostic is replaced by
diagnostic 5FD below with Rev 15.0
Remote
Comm Loss:
Winding Temp
1 Cprsr1A
Circuit Normal Latch All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period
Remote
Comm Loss:
Winding Temp
1 Cprsr2A
Circuit Normal Latch All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period
Remote
Comm Loss:
Winding Temp
2 Cprsr1A
Circuit Normal Latch All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period
Remote
Comm Loss:
Winding Temp
2 Cprsr2A
Circuit Normal Latch All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period
Remote
DDiiaaggnnoossttiiccss

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane Ascend ACR Series and is the answer not in the manual?

Trane Ascend ACR Series Specifications

General IconGeneral
BrandTrane
ModelAscend ACR Series
CategoryChiller
LanguageEnglish

Related product manuals