70
AC-SVX001A-EN
Power Up to Starting
The following diagram shows the timing from a power
up event to energizing the first compressor. The
shortest allowable time would be under the following
conditions:
• No motor restart inhibit time left from subsequent
starts
• Evaporator Water flow occurs quickly with pump on
command
• Power up Start Delay set to 0 minutes
• Need to cool (differential to start) already exists
• Oil level is detected immediately
The above conditions would allow for a minimum
power up to starting the first compressor time of about
45 seconds (variations may exist due to options
installed). Note that it is not advisable to start a chiller
“cold”, the oil heaters should be in operation for a
sufficient length of time prior to first start.
Figure 52. Sequence of events: power up to starting
UC800
Boot Tim e
(25 Sec)
Auto Mode com m anded
by Front Panel or BAS
EXVs self-
close on
power up
Confirm Evaporator Water Flow
(6 Second Filter)
Enforce Restart Inhibit Timer
(0 to 1 minute)
Power Up Delay Inhibit Tim er
(User Adjustable 0 to 30 m inutes)
* Lead compressor (and its lead circuit) is
determined by staging algorithm - “Fixed Staging”
or “Balanced Wear” selection - also influenced by
lockouts, restart inhibit, or diagnostics present.