AC-SVX001A-EN
Table 11. Elastomeric isolator selections
Unit
Size
Isolator Position
1 2 3 4 5 6 7 8 9 10
Standard Length Units
150 Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Brown 61 Brown 61 - -
165 Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Red 62 Red 62 - -
180 Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Red 62 Red 62 - -
200 Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Black 60 Black 60
225 Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Black 60 Black 60
250 Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Black 60 Black 60
275 Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Brown 61 Brown 61
300 Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Brown 61 Brown 61
Extended Length Units
150 Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Brown 61 Brown 61 - -
165 Black 64 Black 64 Black 64 Black 64 Black 64 Black 64 Brown 61 Brown 61 - -
180 Black 64 Black 64 Black 64 Black 64 Black 64 Black 64 Brown 61 Brown 61 - -
200 Black 64 Black 64 Black 64 Black 64 Black 64 Black 64 Brown 61 Brown 61 Brown 61 Brown 61
225 Black 64 Black 64 Black 64 Black 64 Black 64 Black 64 Brown 61 Brown 61 Brown 61 Brown 61
250 Black 64 Black 64 Black 64 Black 64 Black 64 Black 64 Brown 61 Brown 61 Brown 61 Brown 61
275 Black 64 Black 64 Black 64 Black 64 Black 64 Black 64 Brown 61 Brown 61 Brown 61 Brown 61
300 Black 64 Black 64 Black 64 Black 64 Black 64 Black 64 Black 64 Black 64 Brown 61 Brown 61
Compressor Mounting Bolt
Removal
UUnniittss wwiitthh IInnvviissiiSSoouunndd UUllttiimmaattee OOppttiioonn ((MMooddeell
NNuummbbeerr DDiiggiitt 1122 == 33))
For chillers built with InvisiSound Ultimate option,
compressor mounting bolts must be removed to
assure minimum noise during operation. Use a 24mm
socket to remove the (3) M15 x 75mm mounting bolts
for each compressor. They are located under
compressor mounting feet. See figure below.
IImmppoorrttaanntt::
DO NOT DISCARD MOUNTING BOLTS.
Store bolts in the control panel for
future use.
All mounting bolts MUST be reinstalled
prior to compressor removal or unit
move.
NNOOTTIICCEE
EEqquuiippmmeenntt DDaammaaggee!!
FFaaiilluurree ttoo rreeiinnssttaallll bboollttss ccoouulldd ccaauussee sshhiiffttiinngg ooff
ppaarrttss aanndd rreessuulltt iinn eeqquuiippmmeenntt ddaammaaggee..
DDoo nnoott rreemmoovvee ccoommpprreessssoorr oorr mmoovvee uunniitt wwiitthhoouutt
rreeaattttaacchhiinngg ccoommpprreessssoorr mmoouunnttiinngg bboollttss..
Figure 13. Compressor mounting bolt removal
Compressor
Mounting Bolt
Compressor
Mounting
Foot
Isolator
Drainage
Locate the unit near a large capacity drain for water
vessel drain-down during shutdown or repair.
Evaporators are provided with drain connections. A
vent on top of evaporator waterbox prevents vacuum
by allowing air into evaporator for complete drainage.
All local and national codes apply.
IInnssttaallllaattiioonn MMeecchhaanniiccaall

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane Ascend ACR Series and is the answer not in the manual?

Trane Ascend ACR Series Specifications

General IconGeneral
BrandTrane
ModelAscend ACR Series
CategoryChiller
LanguageEnglish

Related product manuals