Voltage (V) Min. Waiting Time (Minutes)
4 15 20 30 40
200 - 240 1.5–5 hp [1.1–3.7
kW]
7.5–60 hp [5.5 –45
kW]
380 - 480 1.5–10 hp [1.1–7.5
kW]
15–125 hp [11–90
kW]
150–350 hp [110–
250 kW]
450–1350 hp
[315–1000 kW]
525-600 1.5–10 hp [1.1–7.5
kW]
15–125 hp [11–90
kW]
525-690 15–125 hp [11–90
kW]
60–550 hp [45–
400 kW]
600–1875 hp
[450–1400 kW]
Be aware that there may be high voltage on the DC link even when the LEDs are turned off.
Before Commencing Repair Work
WARNING
Hazardous Voltage!
1.
Disconnect the adjustable frequency drive from line power.
2.
Disconnect DC bus terminals 88 and 89
3.
Wait at least the time mentioned above in the section General Warning.
4. Remove motor cable
Failure to follow recommendations could result in death or serious injury.
Safety
1-4 TR200 LonWorks