SO-SVN048A-EN 5
General Information
The step-by-step instructions outlined in this manual describe
the procedures required to successfully install an AFDR retrofit
air-cooled Adaptive Frequency Drive™ package in place of an
existing starter on a Trane RTHD helical rotary liquid chillers.
This only applies to chillers having a Tracer
®
AdaptiView™
controller. If the RTHD chiller has a CH530, it must be replaced
with the Tracer AdaptiView RTHD rotary chiller display
upgrade kit (RCDA; sold separately).
The AFDR can be ordered as a close floor mount, remote floor
mount, or remote wall mount. Voltage options include 460/
480 volts, 380/400 volts, and 575/600 volts. D-Frame size
AFDH drive packages can be ordered in a unit-mounted,
stand-mounted, or remote floor-mounted cabinet
configuration. The AFDR units can be equipped with a drive
having a maximum rating of 190 amps, 240 amps, 302 amps,
361 amps, 443 amps, or 535 amps for 460V/480V, and
131 amps, 155 amps, 193 amps, 242 amps, 344 amps, or
400 amps for 575V/600V.
Other Literature Required Before
Ordering or Installing an AFDR
Retrofit
This manual must be used in conjunction with the following
publications:
• Optimus™ Water-Cooled Chillers Model RTHD
Installation, Operation, and Maintenance
(RTHD-SVX01*-EN).
• TR200 Programming Guide (BAS-SVP04*-EN).
• TR200 New D-Frame, 110–400kW Operating Instructions
(BAS-SVX54*-EN).
• RCRA - Tracer
®
AdaptiView™ Rotary Chiller Control
Upgrade For RTHA Chillers Installation Instructions
(SO-SVN030*-EN).
Note: Instructions provided in SO-SVN030*-EN directly
impact AFDR installation; review literature
carefully!