Installation
58 SO-SVN048A-EN
Installation and Startup
Most of the drive parameters are already set up when the drive
is shipped except for a short list of unit specific parameters
obtained from the unit and motor nameplates that need to be
field programmed.
Important: When confirming these parameters it is
important that [0-03 Regional settings] be
left in the “North American” category. Do
NOT change this default setting.
Refer to Table 1 7 for a list of items that are programmed in the
drive at the factory for use with Trane chillers. In the event that
the drive needs to be reset, these parameters need to be
reprogrammed into the drive.
To reset the drive to the Danfoss defaults, perform the following
procedure.
1. Disconnect power to the drive, and wait for the display to
shut down.
2. While powering up the drive, press and hold the following
keys: Status, Main, and OK.
3. After 5 seconds, release the keys.
After the drive is reset, reprogram the items listed in Table 17.
Important: These parameters are supposed to have been
set at the factory to the Trane-specific values
shown here in Table 17. Always confirm before
actual drive start up that this is so and correct
any one of the parameter settings as
necessary.
Table 16. Compressor specific parameters (motor frame/voltage/Hertz)
ID Description
B1/B2 C1/C2 D1/D2/D3
460V/60 Hz 575V/60 Hz 460V/60 Hz 575V/60Hz 460V/60Hz 575V/60Hz
1-21 Motor Power 233HP 233HP 334HP 334HP 441HP 441HP
1-22 Motor Voltage 460V 575V 460V 575V 460V 575V
1-23 Motor Frequency 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz
1-24 Motor Current Output Amps value from new AFDR nameplate sticker; refer to Figure 88, p. 52.
1-25 Motor Nom Speed 3512RPM 3512RPM 3531RPM 3531RPM 3535RPM 3535RPM
1-30 Stator Resistance 0.0303 Ω 0.0430 Ω 0.0201 Ω 0.0308 Ω 0.0122 Ω 0.0197 Ω
1-31 Rotor Resistance 0.0257 Ω 0.0365 Ω 0.0146 Ω 0.0227 Ω 0.0091 Ω 0.0144 Ω
1-35 Main Reactance 5.3684 Ω 8.0570 Ω 3.0050 Ω 4.8857 Ω 2.8882 Ω 4.8553 Ω
1-36 Fe Loss Resistance 188.388 Ω 280.730 Ω 152.612 Ω 243.610 Ω 125.549 Ω 193.850 Ω
3-03 Max Reference 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz
4-14 Mtr Spd High Lim. 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz
14-11 Volt at Mains Fault 391V 489V 391V 489V 391V 489V