12
BAS-SVP042A-EN
3. Select DDiirreecctt CCoonnnneeccttiioonn ((UUSSBB ccaabbllee)) if it is not already selected.
4. Click CCoonnnneecctt and the Unit Summary page displays after successful connection.
Configuration
To configure the UC600 controller:
1. Select the CCoonnttrroolllleerr SSeettttiinnggss UUttiilliittyy tab from right side of the Tracer TU window.
NNoottee:: The content of this screen is based on the type of controller that is connected and the
system protocol used to communicate with the controller.
2. Enter a meaningful name for the controller.
3. Click CCoonnttrroolllleerr UUnniittss to display its contents.
4. Select the preferred units of measure for data communicated across the BACnet link.
5. Click PPrroottooccooll to display its contents.
6. Select the preferred BBaauudd RRaattee in the drop-down list.
NNoottee:: The UC600 device supports four baud rates: 9600, 19200, 38400, and 76800 baud. The
default baud rate is 76800 baud.
7. If the software Device ID is required, check UUssee SSooffttwwaarree DDeevviiccee IIDD and enter a BACnet
Device ID.
8. Click SSaavvee.
9. Cycle power to the device to have the new values take effect.
CCoonnffiigguurriinngg tthhee UUCC660000