EasyManuals Logo
Home>Trane>Controller>Tracer VV550

Trane Tracer VV550 User Manual

Trane Tracer VV550
110 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #75 background imageLoading...
Page #75 background image
CNT-SVX17G-EN 75
Analog Input Calibration
With the Rover service tool, you can calibrate three controller analog inputs:
Space temperature
Space setpoint
Flow sensor
For each input, the calibration value is added to the measured value to determine the
ef
fective value.
Space temperature:
±10.0°F at 0.1°F resolution
Space setpoint:
±10.0°F at 0.1°F resolution
Flow:
Calibrated airflow reading = (gain * actual airflow reading) + offset
Gain = configured airflow measurement gain, 0 to 2, at 0.001 resolution
Offset = configured airflow measurement offset, ±50%, at 0.005% resolution

Table of Contents

Other manuals for Trane Tracer VV550

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane Tracer VV550 and is the answer not in the manual?

Trane Tracer VV550 Specifications

General IconGeneral
BrandTrane
ModelTracer VV550
CategoryController
LanguageEnglish

Related product manuals