CNT-SVX17G-EN 75
Analog Input Calibration
With the Rover™ service tool, you can calibrate three controller analog inputs:
• Space temperature
• Space setpoint
• Flow sensor
For each input, the calibration value is added to the measured value to determine the
ef
fective value.
Space temperature:
±10.0°F at 0.1°F resolution
Space setpoint:
±10.0°F at 0.1°F resolution
Flow:
Calibrated airflow reading = (gain * actual airflow reading) + offset
Gain = configured airflow measurement gain, 0 to 2, at 0.001 resolution
Offset = configured airflow measurement offset, ±50%, at 0.005% resolution