FEATURE Boost BTP feature was disabled while active
Boost Parameters The boost (or BTP) feature parameters may be set via the T1.317
interface or the front panel.
Boost Enabled Parameter enabling and disabling any
form of boost or BTP entry. The hardware
status can also be viewed.
BTP Enabled Parameter DIP switch to enable/disable
external BTP circuitry
Timer Boost Enabled Parameter enabling and disabling
external timer boost or BTP entry or exit.
The hardware status can also be viewed.
Plant State Parameter to toggle between boost (or
BTP) and float states
The following boost (or BTP) parameters may be set/viewed only via
the T1.317 interface:
Auto Mode “TIMED” indicating Timed auto boost, “QRCT”
indicating QRCT auto mode “OFF” indicating no
form of auto boost is selected.
Timed Manual Duration for timed boost, default value is
8 hours, range is 0 to 80 Duration hours,
0 is forever
Auto Multiplication For timed auto boost, boost duration = bd
Factor (AMF) duration * AMF; default value is 5, range
is 1 to 9
Voltage Threshold Quiescent boost entrance voltage
QRCT threshold. 24 volt plant range is 20 to 30
volts, default 26 volts. 48 volt plant range
is 40 to 60 volts, default 52 volts
Current threshold Boost entrance battery current threshold.
QRCT Boost Default value 50 amps
Current/Time QRCT boost exit current gradient
threshold threshold. Default value 0.0 amps/hour
T1.317 Boost usage To activate boost or BTP, use the following command:
OPE DCP,STT=BOOST or
OPE DCP,STT=BTP