Tyco Electronics Galaxy SC Controller J85501F-1
7 - 37 Feature Descriptions Issue 13 February 2001
is known as the Rectifier On Delay (ROD). The default value for the
ROD is 10 minutes. Thus, when the plant voltage drops below the ROT
value for the ROD delay, all rectifiers in standby mode for any reason,
except Tyco Electronics J874 series rectifiers with active Circuit
Breaker Alarms, will turn on.
Invalid Engine
Signals
The Galaxy SC monitors signals from the external engine sequencer
(TR1, TR2, TR3, and TR4), as well as the ETR sequence signal. If all
four TR signals are simultaneously activated, or the ETR signal is
activated longer than the user programmable Engine Time-Out
threshold, then the Galaxy SC assumes there is a problem with the
source of the signals and all the rectifiers are turned back on in an
orderly manner. The Engine Time-Out Threshold is set to 30 minutes as
a default, and can be delayed up to 60 minutes. Zero minutes as a
threshold indicates that this time-out value is to be ignored.
Rectifier Control
Parameters
The following plant control parameters may be set/viewed via the
T1.317 interface or the front panel:
Automatic Rectifier Restart after RFASoftware enabled and disabled, and
view hardware status
Remote Rectifier Turn On- Software enabled and disabled, and
view hardware status
Remote Rectifier Turn Off Software enabled and disabled, and
view hardware status
Internal Rectifier Sequencing- Software enabled and disabled (no
hardware status)
Rectifier On Threshold For 48-volt plants: default 44 volts, range
40 to 50 volts
For 24-volt plants: default 22 volts, range
22 to 25 volts
Operator Rectifier Restart- Restart all rectifiers, no DIP switches
applicable.
Current Viewed in amps
Capacity Based on type, read-only rated capacity
of rectifier
The following plant control features may be set/viewed only via the
T1.317 interface:
Engine-alternator TR Default 1 second, range 0.1 to 600
seconds retirement interval (10 minutes)
Delay before checking RO signal Default 1 second, range 1 to 600
seconds (10 minutes)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Tyco Galaxy SC Controller and is the answer not in the manual?

Tyco Galaxy SC Controller Specifications

General IconGeneral
BrandTyco
ModelGalaxy SC Controller
CategoryController
LanguageEnglish

Related product manuals